Manufacturer: EXTECH Kind of display used: LCD Power supply: battery LR14 1,5V x8 Conform to the norm: EN 61010;CAT IV 600V Measuring instrument features: autoranging;automatic power-off;HOLD function;PEAK HOLD function;MIN/MAX/REL function;low battery indicator Type of meter: insulation resistance Continuity test: acoustic indication;<50Ω Pollution degree: 2 Plug variant: EU Bargraph: yes Measurement: AC voltage;DC voltage;insulation resistance Test voltage: 2.5kV DC;500V DC;1kV DC;5kV DC DC voltage measuring range: 500mV...600V AC voltage measuring range: 500mV...600V Battery/ rechargeable battery: battery LR14 1,5V x8 Insulation resistance measuring ranges: 0.005...6MΩ;60MΩ;600MΩ;6GΩ;60GΩ Display parameters: (6000) DC voltage measuring accuracy: ±(1% + 5 digit) AC voltage measuring accuracy: ±(1% + 5 digit) Insulation resistance measuring accuracy: ±(3% + 15digit) |